Based on 2 g.p.m. @ 1000 F temperature rise, maximum temperature 1670 F. OHM’s per foot cable - both lead
300
400
500
600
650
800
Resistance (R) oer foot
.0000836
.0000625
.0000502
.0000422
.0000388
.0000312
Impedance (Z) per foot
.0000935
.0000855
.0000650
.0000581
.0000524
.0000470
Length MCM
AMPERES CONTINUOUS DUTY CURRENT
300
400
500
600
650
800
3ft
10720.
12400.
13700.
15200.
15800.
17620.
4ft
9300.
10890.
12000.
13100.
13550.
15220.
5ft
8350.
9700.
11400.
11570.
12200.
13420.
6ft
7660.
8800.
9800.
10800.
11100.
12480.
7ft
7060.
8100.
9100.
9900.
10300.
11550.
8ft
6600.
7700.
8500.
9100.
9680.
10720.
9ft
6210.
7100.
8000.
8700.
9160.
10400.
10ft
5900.
6800.
7640.
8300.
8650.
9650.
11ft
5560.
6500.
7250.
7920.
8250.
9100.
12ft
5350.
6200.
6950.
7620.
7920.
8700
13ft
5160.
6000.
6650.
7300.
7600.
8400.
14ft
5000.
5750.
6420.
7000.
7300.
8130.
15ft
4800.
5570.
6200.
6800.
7100.
7780.
16ft
4650.
5400.
6000.
6560.
6820.
7620.
17ft
4500.
5150.
5850.
6360.
6640.
7400.
18ft
4420.
5050.
5670.
6100.
6460
7100.
19ft
4300.
4950.
5540.
6000.
6270.
7000.
20ft
4220.
4850.
5380.
5840.
6110.
6820.
Duty Cycle
Multiplier
100%
1.00
90%
.95
80%
.90
70%
.84
60%
.78
50%
.71
40%
.63
30%
.55
20%
.45
10%
.32
5%
.22
3%
.17
2%
.14

DETERMINING THE PROPER MCM RATING

CABLE SELECTION CHART - MCM

To determine the proper MCM rating, it is first necessary to know (a) the duty cycle, (b) current to be used and (c) length of the cable to be used.
Once this has been determined, proceed as follows, assuming the duty cycle has been set at 20%, the current at 20,000 amperes and the cable length at 7 feet :

(1)     Consult the multiplier chart, uppet left, and at the 20% duty cycle          line you find the multiplier of .45

(2)     Multiply the current required, 20,000 amperes, by .45 and you have          the continuour duty current of the cable, 9,000 amperes.

(3)     Refer  to  the  MCM  rating  chart,  upper  right,  and  find  the cable          length,  7  feet.  Looking  acrose  this  7  foot  line,  find  the   figure          nearest to the continuous duty current of  90,000  amperes,  in  this          case 9,100. The top of this column then shows a 500MCM cable is          required.

 

   TECHNICAL DATA - DUAL - CONDUCTOR CABLES